IL 5881 Varimeter IMD Insulation Monitor

หมวดหมู่สินค้า: IL 5881, SL 5881 VARIMETER IMD Insulation Monitor

15 ธันวาคม 2565

ผู้ชม 451 ผู้ชม

VARIMETER IMD Insulation Monitor

Brand : DOLD

Model : IL 5881, SL 5881

Size : 35 x 90 x 61 mm. , 35 x 90 x 98 mm. 

  • With reference to IEC/EN 61557-8
  • For DC voltage systems up to 12 ... 280 V
  • Wide voltage range of measuring input UN DC 12 ... 280 V

(on request DC 24 ... 500 V with separate auxiliary supply, Measuring range 20 ... 500 kΩ)

  • Adjustable tripping value RAL of 5 ... 200 kΩ or 10 ... 500 kΩ
  • Selective ground fault indication for L+ and L- allows fast fault finding
  • Without auxiliary supply
  • De-energized on trip
  • 2 changeover contacts
  • Automatic or manual reset, programmable
  • With test and reset buttons
  • Connection for external test and reset button possible
  • Galvanic separated AC or DC auxiliary supply available as option
  • Adjustable time delay as option
  • 2 models available:

"- 61 mm deep with terminals near to the bottom to be

 mounted in consumer units or industrial distribution

 systems according to DIN 43880"

"- SL 5881: 98 mm deep with terminals near to the top to be

 mounted in cabinets with mounting plate and cable

 ducts"

  • DIN rail or screw mounting
  • Article number: 0053805
  • Thermoplastic with V0 behaviour according to UL Subjekt 94

เอกสารเพิ่มเติม